| Chiller Module Specifications & Features | |||
| K-O Concepts Models CS | |||
| K-O Concepts Inc. Chiller Part Number | 2542-2700 | ||
| Cooling Type | Refrigeration w/ hermetic compressor. | ||
| Motor type: 24 VDC input w/ electrically commutated motor. | |||
| Refrigerant | R134a (HFC-134a). Refrigerant is CFC- Free. | ||
| Process Coolant Pump | Model MD05: w/ 24 VDC electrically commutated motor. | ||
| Pump type: Centrifugal, magnetically coupled | Note: Pump body is fabricated from engineered plastics. | ||
| (seal-less), water pump. | Note: See performance curves on following page. | ||
| Process Coolant Connections | Two sets of process coolant connections: Connections via Colder | ||
| Products LC series quick-couplings as defined by customer. See K-O | |||
| Interface Control Drawing (ICD) part # 2543-2700. | |||
| Process Coolant Temperature Range | 5.0-7.0°C (typical) with two laser delivery hand-pieces installed. | ||
| Cooling Performance | Process coolant depression from 30-15°C: 20 minutes (typical). | ||
| Note: Performance w/ ambient air @ 30°C | Minimum coolant temperature: 5.0-7.0°C (typical). | ||
| Process Coolant Temperature Stability | ±0.5°C (typical) | ||
| Heat Dissipation | To air (air-cooled) | ||
| Note: Chiller module requires customer fan after installation into | |||
| cabinet. | |||
| Condenser Fan | Motor type: 12 VDC input w/ electrically commutated motor. | ||
| Condenser Fan Control | Chiller utilizes a speed-controlled fan for improved coolant | ||
| temperature control over ambient air temperature range. | |||
| Environment | Indoor operation w/ unrestricted ambient air from 15-30ºC/59-86ºF. | ||
| Process Coolant | 70% distilled water / 30% isopropyl alcohol. | ||
| Process Coolant Capacity | 33 oz. / 1.0 liters | ||
| Note: Volume does not include hand-pieces or external fill bottle. | |||
| Coolant Drain | Coolant drained with chiller pump via drain tube provided. 24 oz. / 0.7 liters is typical coolant recovery volume. | ||
| Heat Exchangers | Condenser: Refrigerant to air heat exchanger (tube & fin design). | ||
| Condenser coil removes heat from refrigerant via fan. | |||
| Evaporator: Refrigerant to water heat exchanger (brazed-plate design). | |||
| Evaporator transfers heat from coolant. | |||
| Input Power Requirements | 24.0 VDC @ 5 amps (typical). Voltage range: 22.7-31.5 VDC. | ||
| Note: 150 watt switching converter power supply optional. | |||
| Electrical Interface Signals | Signals (N.C. / normally closed in passed condition): | ||
| Note: All interface signals are contact closures. | Process water flow (dual channel) & process water level. | ||
| Note: Flow & level switches are reed switch | |||
| type. | |||
| Process Coolant Flow Switch | Set point value: 200 cc/min (each channel). | ||
| Note: Device monitors process coolant flow | Process coolant flow below set point value opens contact. | ||
| through each of “2” customer hand-pieces. | Note: Pump power should be removed if both switches are open. | ||
| Process Level Switch | Process coolant level switch allows for 8 oz. / 0.25 liters loss of coolant | ||
| Note: Device monitors process coolant level in | before opening contacts. | ||
| coolant tank. | |||
| Dimensions (H x W x D) | See K-O Interface Control Drawing (ICD) # 2543-2700 | ||
| Dry Weight | 22.0 lbs / 10.0 kg | ||
| Notes: | |||
| * Data shown is with 15-30°C / 59-86°F (unrestricted) ambient air. | |||
| * Cooling capacity ratings are with process coolant @ 5-7°C / 41-44.6°F. | |||
| * Specifications are subject to change without notice. | |||