Chiller Module Specifications & Features
K-O Concepts Models CS
K-O Concepts Inc. Chiller Part Number 2542-2700
Cooling Type Refrigeration w/ hermetic compressor.                                                                                           
  Motor type:  24 VDC input w/ electrically commutated motor.
Refrigerant R134a (HFC-134a). Refrigerant is CFC- Free.
Process Coolant Pump                                                  Model MD05:   w/ 24 VDC electrically commutated motor.                                                                                                                             
Pump type: Centrifugal, magnetically coupled Note:  Pump body is  fabricated from engineered plastics. 
(seal-less), water pump. Note:  See performance curves on following page.
Process Coolant Connections Two sets of process coolant connections:  Connections via Colder 
  Products LC series quick-couplings as defined by customer.  See K-O 
  Interface Control Drawing (ICD) part # 2543-2700.   
Process Coolant Temperature Range 5.0-7.0°C (typical) with two laser delivery hand-pieces installed. 
Cooling Performance                                                     Process coolant depression from 30-15°C:  20 minutes (typical).                       
Note:  Performance w/ ambient air @ 30°C Minimum coolant temperature: 5.0-7.0°C (typical).
Process Coolant Temperature Stability ±0.5°C (typical)
Heat Dissipation To air (air-cooled)
  Note:  Chiller module requires customer fan after installation into
  cabinet.
Condenser Fan Motor type:  12 VDC input w/ electrically commutated motor.
Condenser Fan Control Chiller utilizes a speed-controlled fan for improved coolant
  temperature control over ambient air temperature range.
Environment Indoor operation w/ unrestricted ambient air from 15-30ºC/59-86ºF.
Process Coolant 70% distilled water / 30% isopropyl alcohol.
Process Coolant Capacity  33 oz. / 1.0 liters
  Note:  Volume does not include hand-pieces or external fill bottle.
Coolant Drain Coolant drained with chiller pump via drain tube provided.  24 oz. / 0.7 liters is typical coolant recovery volume.   
Heat Exchangers  Condenser:  Refrigerant to air heat exchanger (tube & fin design).  
  Condenser coil removes heat from refrigerant via fan.
  Evaporator:  Refrigerant to water heat exchanger (brazed-plate design).   
  Evaporator transfers heat from coolant.
Input Power Requirements 24.0 VDC @ 5 amps (typical). Voltage range:  22.7-31.5 VDC.
  Note:  150 watt switching converter power supply optional.
Electrical Interface Signals                                                                                                Signals (N.C. / normally closed in passed condition):                                            
Note:  All interface signals are contact closures.  Process water flow (dual channel) & process water level.
Note:  Flow & level switches are reed switch  
 type.  
Process Coolant Flow Switch                                     Set point value:  200 cc/min (each channel).                                                                                                          
Note:  Device monitors process coolant flow  Process coolant flow below set point value opens contact.
through each of “2” customer hand-pieces.  Note:  Pump power should be removed if both switches are open.
Process Level Switch                                                  Process coolant level switch allows for 8 oz. / 0.25 liters loss of coolant 
Note:  Device monitors process coolant level in  before opening contacts.
coolant tank.  
Dimensions (H x W x D) See K-O Interface Control Drawing (ICD) # 2543-2700
Dry Weight  22.0 lbs / 10.0 kg
Notes:
*     Data shown is with 15-30°C / 59-86°F (unrestricted) ambient air.
*     Cooling capacity ratings are with process coolant @ 5-7°C / 41-44.6°F.
*     Specifications are subject to change without notice.   