| Chiller Module Specifications & Features | ||||
| K-O Concepts Models HS-4 | ||||
| K-O Concepts Inc. Chiller Part Number | 2543-2650 | |||
| Cooling Capacity | 400 watts / 1,360 BTU typical capacity w/ 20°C refrigerant | |||
| 115 VAC, 60 Hz Model | 250 watts / 850 BTU typical capacity w/ 10°C refrigerant | |||
| Cooling Capacity | 400 watts / 1,360 BTU typical capacity w/ 20°C refrigerant @ 60 Hz | |||
| 220 VAC, 50 / 60 Hz Model | 300 watts / 1,025 BTU typical capacity w/ 20°C refrigerant @ 50 Hz | |||
| Refrigerant Delivery | Type R134a refrigerant delivered via 8 ft. long flexible hoses. | |||
| Optional Cooling Applications | Remote forced air evaporator assembly available for electronics | |||
| cabinet cooling applications. | ||||
| Mounting | Standard 19-inch rack-mounted configuration. | |||
| Environment | Indoor operation w/ unrestricted ambient air from 15-30ºC/59-86ºF w/ | |||
| relative humidity from 10-90% (non condensing). | ||||
| Temperature Stability | Refrigerant temperature operational range: 7-20°C ±0.5°C. | |||
| Heat Dissipation | To air (air-cooled) | |||
| Condenser Fan | AC Axial Type: 70 CFM @ 0.12 inches static pressure typical | |||
| Compressor Type | Hermetic | |||
| Environment | Indoor operation w/ unrestricted ambient air from 15-30ºC/59-86ºF. | |||
| Refrigerant Type | All models use R134a (HFC-134a). Refrigerant is CFC - Free. | |||
| Input Voltage & Frequency Requirements | Model HS-4 / 115: 115 VAC, 1Ø, 60 Hz | |||
| Model HS-4 / 220: 220 VAC, 1Ø, 50 Hz | ||||
| Current Draw | Model HS-4 / 115: 3.2 A @ 60 Hz (Typical) | |||
| Model HS-4 / 220: 1.8 A @ 50 Hz (Typical) | ||||
| Circuit Breaker | Model HS-4 / 115: 7 A @ 250 VAC (single pole) | |||
| Model HS-4 / 220: 5 A @ 250 VAC (single pole) | ||||
| AC Power Inlet | IEC 60320 compatible | |||
| Air Filter | Cleanable filter installed and spare filter pack shipped with unit. | |||
| Cabinet Dimensions (H x W x D) | All Models: 6.5 x 17.5 x 7.5 inches | |||
| Front Panel Dimensions (H x W) | All Models: 7.0 (4 units) x 19.0 inches | |||
| Dry Weight | 26.0 lbs / 11.8 kg | |||
| Notes: | ||||
| * Cooling capacity ratings are @ 30°C / 86°F. | ||||
| * Call for cooling capacities @ return air temperatures other than those listed. | ||||
| * See Thermal Performance chart for cooling capacities @ other process temperatures. | ||||
| * Specifications are subject to change without notice. | Page 3 of 4 | |||